The L60 provides fast and secure sub-cycle phase comparison protection, for both two-terminal and three-terminal lines, lines with series compensation and for single-pole and three-pole tripping applications. The L60 can operate using existing power line carrier or fiber optic communications, and compensates for channel asymmetry and charging currents. The L60 can provide complete support of dual-breaker line terminals by using multiple current inputs.

Multilin L60

Line Phase Comparison System

The L60 provides fast and secure sub-cycle phase comparison protection, for both two-terminal and three-terminal lines, lines with series compensation and for single-pole and three-pole tripping applications. The L60 can operate using existing power line carrier or fiber optic communications, and compensates for channel asymmetry and charging currents. The L60 can provide complete support of dual-breaker line terminals by using multiple current inputs.

New and Enhanced Communication Capabilities
  • Support switchable IEC 61850 Ed. 1 and Ed. 2 and redundant SNTP (FW 7.7x)
  • New UR front panel with integrated 7” color, graphical display - providing operators with enhanced situational awareness (FW 7.6x)
  • High density I/O module supporting up to 120 inputs or up to 72 contact outputs – eliminating the need for additional discrete devices (FW 7.6x)
Cyber Security - CyberSentry UR (FW v7.xx)

CyberSentryTM enables UR devices to deliver full cyber security features that help customers to comply with cyber security requirements (NERC CIP, IEEE 1686, IEC 62443, etc):

  • Secured firmware upgrade: FW file includes hash code that enables authentication prior to being used for upgrading UR Relay (FW 7.9x)
Extended Oscillography Records (FW v7.xx)
  • Increased number of digital and analog channels (FW 7.90)
  • Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE 2013 standard (FW v7.40)
  • Configurable events allow for records of up to 45s at 64 samples per cycle
New and Enhanced Protection and Control Functionality
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)

Key Features

  • Line current differential with adaptive restraint
  • Stub bus protection
  • Breaker failure
  • Three-pole autoreclose
  • Underfrequency protection
  • Phase directional overcurrent, neutral directional with dual polarity criteria, broken conductor and thermal overload
  • Non-directional overcurrent: phase, neutral and negative sequence
  • Phase over/under voltage, negative sequence overvoltage
  • Two independent synchronism check elements
 

Protection & Control

The L60 is an advanced sub-cycle phase comparison relay intended for application on overhead transmission lines, including series-compensated lines, and underground cables of different voltage levels. Two and three-terminal lines can be protected easily by interfacing to new or existing power line carrier equipment. The L60 also has built-in interfaces to support communication channels of various types between line terminals. Part of the Universal Relay family, the L60 comes with a variety of versatile features, truly integrating protection, monitoring, metering, communication and control in one easy-to-use device. The Universal Relay family offers a high degree of modularity in its design and functionality, providing superior performance in protection and control, while meeting the toughest requirements of the marketplace.

 

Functional Block Diagram

L60 Block Diagram

ANSI® Device Numbers & Functions

Device NumberFunction
21GPhase Distance
21PGround Distance
25Synchrocheck
27PPhase Undervoltage
27XAuxiliary Undervoltage
32NWattmetric Zero-Sequence Directional
49Thermal Overload
50BFBreaker Failure
50DDCurrent Disturbance Detector
50GGround Instantaneous Overcurrent
Device NumberFunction
50NNegative Sequence Instantaneous Overcurrent
50PPhase Instantaneous Overcurrent
50_2Negative Sequence Instantaneous Overcurrent
51GGround Time Overcurrent
51NNegative Sequence Time Overcurrent
51PPhase Time Overcurrent
51_2Negative Sequence Time Overcurrent
52AC Circuit Breaker
59NNeutral Overvoltage
Device NumberFunction
59PPhase Overvoltage
59XNegative Sequence Directional Overcurrent
67NNeutral Directional Overcurrent
67PPhase Directional Overcurrent
67_2Negative Sequence Directional Overcurrent
68Power Swing Blocking
78Out-of-Step Tripping
79Autoreclose
87PCPhase Comparison

Key Features

  • Breaker condition monitoring including breaker arcing current (I2t) and trip counter
  • Metering - current, voltage, power, energy and frequency
  • Oscillography - 64 samples/cycle, up to 64 records
  • Event Recorder - 1024 time tagged events, with 0.5ms scan of digital inputs
  • Data Logger- Up to 16 channels with user-selectable sampling rate
  • Fault Locator

Monitoring & Diagnostics

Monitoring & Diagnostics The L60 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems.

Advanced Automation

The L60 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average line differential relay. The L60 integrates seamlessly with other UR relays for complete system protection.

FlexLogic™ diagram FlexLogic™ allows for the customization of the L60 for custom protection, control and automation, allowing users to build line protection schemes and applications for their requirements.

Key Features

  • Three independent 100Mbps Ethernet ports enable purpose specific LAN support that eliminates latency effect of heavy traffic protocols on mission critical communication services
  • Embedded IEEE 1588 time synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Direct I/O secures high-speed exchange of binary data between URs
  • Increase network availability by reducing failover time to zero through IEC62439-3 “PRP” support

Advanced Communications

The L60 provides for secure remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available three independent and redundant Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner. 
The L60 supports the most popular industry standard protocols enabling easy, direct integration into monitoring and SCADA systems.

  • DNP 3.0 (serial & TCP/IP)
  • IEC 60870-5-103 and IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  • HTTP, TFTP, SFTP and MMS file transfer
  • Redundant SNTP and IEEE 1588 for time synchronization
  • PRP as per IEC 62439-3
  • Supports Routable GOOSE (R-GOOSE)
HardFiber diagram

Cyber Security - CyberSentry™ UR (FW v7.4xx)

CyberSentry enables UR devices to deliver full cyber security features that help customers to comply with NERC CIP and NITIR 7628 cyber security requirements through supporting the following core features:

Secure FW upgrade

UR FW files v7.9 and up now include a hash code that allows for authentication prior to being used for upgrading UR devices.

Password Complexity

Supporting up to 20 alpha- numeric or special characters, UR passwords exceed NERC CIP requirements for password complexity. Individual passwords per role are available.

AAA Server Support (Radius)

Enables integration with centrally managed authentication and accounting of all user activities and uses modern industry best practices and standards that meet and exceed NERC CIP requirements for authentication and password management.

Role Based Access Control (RBAC)

Efficiently administrate users and roles within UR devices. The new and advanced access functions allow users to configure up to five roles for up to eight configurable users with independent passwords. The standard “Remote Authentication Dial In User Service” (Radius) is used for authentication.

Event Recorder (Syslog for SEM)

Capture all cyber security related events within a SOE element (login, logout, invalid password attempts, remote/local access, user in session, settings change, FW update, etc), and then serve and classify data by security level using standard Syslog data format. This enables UR devices integration with established SEM (Security Event Management) systems.

EnerVista™ Software

The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the L60 relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the L60 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. 

Learn More

 

Enervista Software

The L30 is a cost-effective line current differential protection relay intended for sub-transmission and medium voltage lines and cables providing reliable and secure operation even under the worst case power system conditions. The L30 provides secure high-speed fault detection and clearance suitable for three-pole tripping applications. The L30 supports inter-relay communications via direct fiber as well as standard RS422, G.703 and C37.94 telecommunication interfaces. The L30 also provides synchrophasor measurements over Ethernet per IEEE C37.118.

Multilin L30

Line Current Differential System

The L30 is a cost-effective line current differential protection relay intended for sub-transmission and medium voltage lines and cables providing reliable and secure operation even under the worst case power system conditions. The L30 provides secure high-speed fault detection and clearance suitable for three-pole tripping applications. The L30 supports inter-relay communications via direct fiber as well as standard RS422, G.703 and C37.94 telecommunication interfaces. The L30 also provides synchrophasor measurements over Ethernet per IEEE C37.118.

New and Enhanced Communication Capabilities

  • New process bus module supports IEC 61869 sample values, PTP master capabilities and SV switching (FW 7.9x)
  • New UR process bus modules supporting IEC61850-9-2LE Merging Units and IEC61850-9-2 Hardfiber (FW 7.8x) Module Training available here
  • Support switchable IEC 61850 Ed. 1 and Ed. 2 and redundant SNTP (FW 7.7x)
  • New UR front panel with integrated 7” color, graphical display - providing operators with enhanced situational awareness (FW 7.6x)
  • High density I/O module supporting up to 120 inputs or up to 72 contact outputs – eliminating the need for additional discrete devices (FW 7.6x)

Cyber Security - CyberSentry UR (FW v7.xx)

CyberSentryTM enables UR devices to deliver full cyber security features that help customers to comply with cyber security requirements (NERC CIP, IEEE 1686, IEC 62443, etc):

  • Secured firmware upgrade: FW file includes hash code that enables authentication prior to being used for upgrading UR Relay (FW 7.9x)

Fully Compatible with IEC 61850-9-2LE or IEC61869 process bus schemes:

  • Can connect to up to 8 merging units over -9-2LE or 61869
  • Supports PRP, HSR, dual HSR and point-to-point process bus topology
  • Provides support for GE Vernova’s IEC 61850 HardFiber Process Bus Solution

Extended Oscillography Records (FW v7.xx)

  • Increased number of digital and analog channels (FW 7.90)
  • Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE 2013 standard (FW v7.40)
  • Configurable events allow for records of up to 45s at 64 samples per cycle

New and Enhanced Protection and Control Functionality

  • New dedicated Inrush detection element (FW 8.0)
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)

Key Features
  • Line current differential with adaptive restraint
  • Stub bus protection
  • Breaker failure and three-pole autoreclose
  • Underfrequency protection and dedicated harmonic inrush detection
  • Phase directional overcurrent, neutral directional with dual polarity criteria, broken conductor and thermal overload
  • Non-directional overcurrent: phase, neutral and negative sequence
  • Phase over/under voltage, negative sequence overvoltage
  • Two independent synchronism check elements
Protection & Control

The L30 is a cost-effective line current differential protection relay intended for sub-transmission and medium voltage lines and cables, providing reliable and secure operation even under the worst case power system conditions. The L30 provides secure high-speed fault detection and clearance suitable for three-pole tripping applications. Part of the Universal Relay family, the L30 comes with a variety of versatile features, truly integrating protection, monitoring, metering, communication and control in one easy-to-use device. The Universal Relay family offers a high degree of modularity in its design and functionality, providing superior performance in protection and control, while meeting the toughest requirements of the marketplace.

Functional Block Diagram
l30-block-diagram-02
ANSI® Device Numbers & Functions
Device NumberFunction
25Synchrocheck
27PPhase Undervoltage
27XAuxiliary Undervoltage
49Thermal Overload
50BFBreaker Failure
50DDCurrent Disturbance Detector
50GGround Instantaneous Overcurrent
50NNeutral instantaneous overcurrent
50PPhase Instantaneous Overcurrent
Device NumberFunction
50_2Negative Sequence Instantaneous Overcurrent
51GGround Time Overcurrent
51NNeutral Time Overcurrent
51PPhase Time Overcurrent
51_2Negative Sequence Time Overcurrent
52AC Circuit Breaker
59_2Negative Sequence Overvoltage
59NNeutral overvoltage
59PPhase Overvoltage
59_2Negative-sequence overvoltage
Device NumberFunction
59XAuxiliary overvoltage
67NNeutral Directional Overcurrent
67PPhase Directional Overcurrent
79Automatic Recloser
81RRate of change frequency
81UUnderfrequency
87LSegregated Line Current Differential
87LGGround Line Current Differential
 Harmonic/Inrush detection

Key Features
  • Real-time monitoring of remote, local and differential per phase currents
  • Oscillography - 64 samples/cycle, up to 64 records
  • Event Recorder - 1024 time tagged events, with 0.5ms scan of digital inputs
  • Data Logger - Up to 16 channels with user-selectable sampling rate
  • P & M class synchrophasors of voltage, current and sequence components – 1 to 120 frames/sec
 

Monitoring & Diagnostics

monitoring The L30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.

Advanced Automation

The L90 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average line relay. The L90 integrates seamlessly with other UR relays for complete system protection.

FlexLogic™ diagram FlexLogic allows for the customization of the L30 to operate and control the breakers and other auxiliary devices needed to fit most line protection schemes and applications.

Key Features

Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P & C life cycle costs

  • Three independent 100Mbps Ethernet ports enable purpose specific LAN support that eliminates latency effect of heavy traffic protocols on mission critical communication services
  • Embedded IEEE 1588 time-synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Direct I/O secures high-speed exchange of binary data between URs
  • Increase network availability by reducing failover time to zero through IEC62439-3 PRP, HSR or dual HSR support
Advanced Communications

The L30 provides for secure remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available three independent and redundant Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner.

The L30 supports the most popular industry standard protocols enabling easy, direct integration into monitoring and SCADA systems.

  • IEC 61850-9-2LE networked or IEC61850-9-2 Hardfiber process bus support
  • DNP 3.0 (serial & TCP/IP)
  • IEC 60870-5-103 and IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  • HTTP, TFTP, SFTP and MMS file transfer
  • Redundant SNTP and IEEE 1588 for time synchronization
  • PRP as per IEC 62439-3
  • IRC module that combines C37.92 multimode and direct connection singlemode
  • Supports Routable GOOSE (R-GOOSE)
Interoperability with Enbedded IEC 61850

Use the L30 with integrated IEC 61850 to lower costs associated with generator protection, control and automation. GE Vernova’s leadership in IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.

hardfiber

The L30’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. 

Learn More

The L30 can also connect to GE Vernova MU320 or third-party merging units using standard IEC 61869 or IEC 61850-9-2LE communication protocols.

Cyber Security - CyberSentry™ UR (FW v7.4xx)

CyberSentry enables UR devices to deliver full cyber security features that help customers to comply with NERC CIP and NITIR 7628 cyber security requirements through supporting the following core features:

Secure FW upgrade

UR FW files v7.9 and up now include a hash code that allows for authentication prior to being used for upgrading UR devices.

Password Complexity

Supporting up to 20 alpha- numeric or special characters, UR passwords exceed NERC CIP requirements for password complexity. Individual passwords per role are available.

AAA Server Support (Radius)

Enables integration with centrally managed authentication and accounting of all user activities and uses modern industry best practices and standards that meet and exceed NERC CIP requirements for authentication and password management.

Role Based Access Control (RBAC)

Efficiently administrate users and roles within UR devices. The new and advanced access functions allow users to configure up to five roles for up to eight configurable users with independent passwords. The standard “Remote Authentication Dial In User Service” (Radius) is used for authentication.

Event Recorder (Syslog for SEM)

Capture all cyber security related events within a SOE element (login, logout, invalid password attempts, remote/local access, user in session, settings change, FW update, etc), and then serve and classify data by security level using standard Syslog data format. This enables UR devices integration with established SEM (Security Event Management) systems.

EnerVista™ Software

The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the L30 relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the L30 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. 

Learn More

 

Enervista Software

The MiCOM Agile P44T is a multifunctional protection device, supplementing distance main protection with a host of backup protection, thermal protection, recording, control, measurement and monitoring features. It provides fast, highly selective railway catenary distance protection combined with the delta directional decision proven technique. The trip time is typically 0.7 to 1 cycle. Five zones of protection with quadrilateral characteristics allow versatile deployment as the main protection for all AC catenary/feeder systems.

MiCOM Agile P44T

Catenary Distance Protection

The MiCOM Agile P44T is a multifunctional protection device, supplementing distance main protection with a host of backup protection, thermal protection, recording, control, measurement and monitoring features. It provides fast, highly selective railway catenary distance protection combined with the delta directional decision proven technique. The trip time is typically 0.7 to 1 cycle. Five zones of protection with quadrilateral characteristics allow versatile deployment as the main protection for all AC catenary/feeder systems.

What's New

Enhanced Ethernet board module with switchable Ethernet redundancy delivered in a single model.

It supports PRP, HSR and RSTP in one model, allowing a single P40 model to be used in any application requiring redundant Ethernet communications. The new module is designed to handle high density traffic in the IEC 61850-8-1 network, with time latency halved. Larger architecture digital substations can also be supported, with up to 50 nodes now possible in HSR rings.

Key Features & Benefits:

  • Universal IRIG-B – Modulated and demodulated supported in the same model
  • HSR Ring – Extended to 50 node support for larger substation architectures
  • Fast performance, particularly in onerous applications such as where process bus GOOSE is used for tripping purposes

Overview

Many high speed, regional and urban rail networks worldwide are electrified. The exposed nature of overhead catenaries makes them fault-prone and protection devices are vital for selective tripping and isolation of any faulted section.

The MiCOM P44T Agile detects and trips faults in less than one power system cycle. This minimises the risk of downed conductors, making successful supply restoration more likely and ultimately minimising delays to trains.

Comprehensive backup protections and advanced communications make MiCOM P44T suitable for railway protection for classic or auto transformer-fed catenaries at 50 Hz and 60Hz.

Key Benefits
  • User programmable operate/reset curves for thermal, overcurrent and earth fault protection
  • Loss of field and out of step, anti backspin and loss of load, 3 phase volt check, phase reversal, VTS and CTS
  • Comprehensive start sequence and re-acceleration scheme
  • RTD and CLIO (current-loop I/O) available as hardware options
  • 2 independent setting groups
  • Option of up to 10 RTD inputs, with a selection of different RTD types

Key benefits:

  • Sub-cycle fault clearance from 0.7 to 1 cycle
  • Load blinder prevents spurious trips cascading through the network
  • Integral digital teleprotection between line ends
  • Multi-shot autoreclosure with check synchronism
  • InterMiCOM option for end-to-end protection communications
  • Delta I protection elements reliably detect high impedance faults
  • Wrong phase coupling, panto flash over and train startup protection

Functional Block Diagram

Agile P44T Enhanced-diagram

ANSI ® Device Numbers and Functions

Device NumberFunction
21Distance
25Check Synchronizing
27Undervoltage
49Thermal Overload
50/27Switch-on to Fault
50Phase Definite Time Overcurrent
51Phase Inverse-Time Overcurrent
52Breaker and Isolator Control

 

Device NumberFunction
59Overvoltage
67Directional Phase Overcurrent
68Power Swing Blocking
79Autoreclose
85InterMiCOM Teleprotection
86Latching/Lockout Contacts
21BLLoad Encroachment/Blinder

 

Device NumberFunction
21FLFault Locator
50BFCB Failure
PSLProgrammable Logic
VTSVT Supervision
DEFDefrost Protection
PFOPanto Flashover
WFCWrong Phase Coupler
DlzDelta I for high impedance faults

MiCOM S1 Agile

Key benefits:

  • Powerful, free of charge, PC toolsuite
  • Optimum management of the installed base, structured as per the substation topology
  • Intuitive and versatile interface with file management facilities
  • Logical structure based on substation, voltage level and bay
  • Version control and cross-checking facilities for IED settings
  • Real-time measurement visualization – MiCOM S1 Agile extends to all MiCOM Agile IEDs - including P847 PMU and busbar schemes

Engineering Tool Suite

S1 Agile is the truly universal PC tool for MiCOM Agile relay, assemble all tools in a palette for simple entry, with intuitive navigation via fewer mouse-clicks. No-longer are separate tools required for redundant Ethernet configuration, phasor measurement unit commissioning, busbar scheme operational dashboards, programmable curve profiles or automatic disturbance record extraction – applications are embedded. MiCOM S1 Agile supports all existing MiCOM, K-Series and Modulex, including a utility for automatic conversion of setting files from previous generations of numerical relays like K-series and MiCOM P20 to the latest P40 Agile models.

To move to the future, with no loss of functionality, no loss of device support, and full compatibility with your installed base and system architecture – request a copy of S1 Agile with the contact form link below.

micom-screen

Key features in the MiCOM S1 family:

  • GE Vernova\’s integrated engineering tool that provides users with access to automation IED configuration and record data
  • Integrated configuration and monitoring features
  • Send and extract setting files
  • Event and disturbance record extraction and analysis

MiCOM S1 Agile software request

To receive the MiCOM S1 Agile, please use our Contact form. This will also ensure that you are kept up-to-date with the latest enhancements, including updates and bug fixes.

Refurbishment Solutions

GE Vernova’s latest MiCOM P240 models offer a perfect functional match for our MCHN,MCHG, MOPN and Motpro relays from the heritage installed-base brands of GEC Measurements, GEC Alsthom, GE VERNOVA and Areva:

Refurbishment Solutions – “If It’s Blue Think to Renew”

GE Vernova\’s latest MiCOM P440 Catenary Distance Protection offers a perfect functional replacement to our “LFZP 141” Catenary Distance relays, from the heritage installed-base brands GEC Measurements, GEC Alsthom and GE VERNOVA. With substantially improved speed, optimized and advanced algorithms, the new MiCOM P44T retains form, fit and function compatibility but delivers the latest platform and software ready for today\’s environment, and for future-proofed application for the decades ahead.

LFZP 141 Replacement:

Form, fit and functional compatibility – the P44T case 80TE fits in the same panel or rack space

Contact us for advice and support

Line Distance Protection System

The D60 is suitable for protecting transmission lines and cables including lines equipped with series compensation. The D60 supports dual-breaker applications and can be applied in single-pole or three-pole tripping applications. The D60 is applicable to different teleprotection schemes and includes inter-relay protection communications via direct fiber as well as different interfaces. The D60 also provides synchrophasor measurement over Ethernet per IEEE C37.118.

Multilin D60

Line Distance Protection System

The D60 is suitable for protecting transmission lines and cables including lines equipped with series compensation. The D60 supports dual-breaker applications and can be applied in single-pole or three-pole tripping applications. The D60 is applicable to different teleprotection schemes and includes inter-relay protection communications via direct fiber as well as different interfaces. The D60 also provides synchrophasor measurement over Ethernet per IEEE C37.118.

New and Enhanced Communication Capabilities
  • New UR process bus modules supporting IEC61850-9-2LE Merging Units and IEC61850-9-2 Hardfiber (FW 7.8x) Module Training available here
  • Support switchable IEC 61850 Ed. 1 and Ed. 2 and redundant SNTP (FW 7.7x)
  • New UR front panel with integrated 7” color, graphical display - providing operators with enhanced situational awareness (FW 7.6x)
  • High density I/O module supporting up to 120 inputs or up to 72 contact outputs – eliminating the need for additional discrete devices (FW 7.6x)
Cyber Security - CyberSentry UR (FW v7.xx)

CyberSentryTM enables UR devices to deliver full cyber security features that help customers to comply with cyber security requirements (NERC CIP, IEEE 1686, IEC 62443, etc):

  • Secured firmware upgrade: FW file includes hash code that enables authentication prior to being used for upgrading UR Relay (FW 7.9x)
Fully Compatible with GE Vernova's Multlilin HardFiber System - Provides support for GE Vernova's IEC 61850 HardFiber Process Bus Solution:

Complete IEC 61850 Process Bus Solution providing resource optimization and minimizing total P&C life cycle costs. 

Learn more

Extended Oscillography Records (FW v7.xx)
  • Increased number of digital and analog channels (FW 7.90)
  • Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE 2013 standard (FW v7.40)
  • Configurable events allow for records of up to 45s at 64 samples per cycle
New and Enhanced Protection and Control Functionality (FW version 5.90)
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)
  • Added backup protection functions with sensitive reverse power element "32S" 
  • Added over/under/rate of change of frequency elements 
  • New thermal overload element 
  • New broken conductor element 
  • Customizable version of the POTT and DCB schemes "POTT1 and DCB1" (FW v7.20)
  • Neutral directional overcurrent with dual polarity criteria "67N" (FW v 7.20)
Protection and Control Functionality
  • 6-distance zones and sub-cycle performance SW options (FW 8.0)
  • New TGFD and Inrush detection elements (FW 8.0)
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)

Key Features

  • Up to six phase distance with independent compensation settings for in-zone power transformers
  • Up to six ground distance with independent self and mutual zero-sequence compensation
  • Sub-cycle distance performance available
  • Out-of-step tripping and power swing blocking
  • Synchronism check for dual-breaker applications
  • Four-shot dual-breaker autorecloser
  • VT fuse failure detector, compensated overvoltage
  • Phase and negative sequence directional overcurrent, neutral directional with dual polarity criteria, broken conductor, TGFD thermal overload and more.

Protection & Control

The D60 is a high-end, cost-effective distance protection relay intended for protecting transmission lines and cables, providing reliable and secure operation even under the worst case power system conditions. Part of the Universal Relay family, the D60 comes with a variety of versatile features, truly integrating protection, monitoring, metering, communication and control in one easy-to-use device. The Universal Relay family offers a high degree of modularity in its design and functionality, providing superior performance in protection and control, while meeting the toughest requirements of the marketplace.

Functional Block Diagram
d60-block-diagram-02
Device NumberFunction
21GGround Distance
21PPhase Distance
25Synchrocheck
27PPhase Undervoltage
27XAuxiliary Undervoltage
32Sensitive Directional Power
49Thermal Overload
50BFBreaker Failure
50DDCurrent Disturbance Detector
50GGround Instantaneous Overcurrent
50NNeutral Instantaneous Overcurrent
Device NumberFunction
50PPhase Instantaneous Overcurrent
50_2Negative Sequence Instantaneous Overcurrent
51GGround Time Overcurrent
51NNeutral Time Overcurrent
51PPhase Time Overcurrent
51_2Negative Sequence Time Overcurrent
52AC Circuit Breaker
59CCompensated Overvoltage
59NNeutral Overvoltage
59PPhase Overvoltage
Device NumberFunction
59XAuxiliary Overvoltage
59_2Negative Sequence Overvoltage
67NNeutral Directional Overcurrent
67PPhase Directional Overcurrent
67_2Negative Sequence Directional Overcurrent
68Power Swing Blocking
78Out-of-Step Tripping
79Automatic Recloser
81U/OUnder/Over Frequency, df/dt
ROCOFRate of Change of Frequency

Key Features
  • P & M class synchrophasors of voltage, current and sequence components – 1 to 120 frames/sec
  • Metering - current, voltage, power, energy, frequency
  • Oscillography – analog and digital parameters at 64 samples/cycle
  • Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs
  • Setting for security audit trails for tracking changes to D60 configurations
Monitoring & Diagnostics
Monitoring & Diagnostics The D60 is the single point for protection, control, metering, and monitoring in one integrated device that can be easily connected directly to HMI or SCADA monitoring and control systems.
Advanced Automation

The D60 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average line protection relay. The D60 integrates seamlessly with other UR relays for complete system protection, including unit and auxiliary transformers, and balance of plant protection.

FlexLogic™ diagram FlexLogic™ allows for the customization of D60 for custom protection, control and automation, allowing users to build line protection schemes and applications for their equipment.

Key Features

Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P & C life cycle costs

  • Three independent 100Mbps Ethernet ports enable purpose specific LAN support that eliminates latency effect of heavy traffic protocols on mission critical communication services
  • Embedded IEEE 1588 time-synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Direct I/O secures high-speed exchange of binary data between URs
  • Increase network availability by reducing failover time to zero through IEC62439-3 PRP, HSR or dual HSR support
Advanced Communications

The D60 provides for secure remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information.The available three independent and redundant Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner. 
The D60 supports the most popular industry standard protocols enabling easy, direct integration into monitoring and SCADA systems.

  • IEC 61850-9-2LE or IEC 61869 point-to-point or networked networked or IEC61850-9-2 Hardfiber process bus support
  • DNP 3.0 (serial & TCP/IP)
  • IEC 60870-5-103 and IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  • HTTP, TFTP, SFTP and MMS file transfer
  • Redundant SNTP and IEEE 1588 for time synchronization
  • PRP as per IEC 62439-3
  • IRC module that combines C37.92 multimode and direct connection singlemode
  • Supports Routable GOOSE (R-GOOSE)
Interoperability with Enbedded IEC 61850

Use the D60 with integrated IEC 61850 to lower costs associated with line distance protection, control and automation. GE Vernova’s leadership in IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.

 

 

HardFiber system

The D60’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. Learn more

The D60 can also connect to GE Vernova MU320 or third-party merging units using standard IEC 61869 or IEC 61850-9-2LE communication protocols.

Cyber Security - CyberSentry™ UR (FW v7.4xx)

CyberSentry enables UR devices to deliver full cyber security features that help customers to comply with NERC CIP and NITIR 7628 cyber security requirements through supporting the following core features:

Secure FW upgrade

UR FW files v7.9 and up now include a hash code that allows for authentication prior to being used for upgrading UR devices.

Password Complexity

Supporting up to 20 alpha- numeric or special characters, UR passwords exceed NERC CIP requirements for password complexity. Individual passwords per role are available.

AAA Server Support (Radius)

Enables integration with centrally managed authentication and accounting of all user activities and uses modern industry best practices and standards that meet and exceed NERC CIP requirements for authentication and password management.

Role Based Access Control (RBAC)

Efficiently administrate users and roles within UR devices. The new and advanced access functions allow users to configure up to five roles for up to eight configurable users with independent passwords. The standard “Remote Authentication Dial In User Service” (Radius) is used for authentication.

Event Recorder (Syslog for SEM)

Capture all cyber security related events within a SOE element (login, logout, invalid password attempts, remote/local access, user in session, settings change, FW update, etc), and then serve and classify data by security level using standard Syslog data format. This enables UR devices integration with established SEM (Security Event Management) systems.

EnerVista™ Software

The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the D60 relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the D60 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. Learn More

EnerVista Software

Part of the MiCOM P40 platform, the Agile P441, P442 and P444 numerical full scheme distance relays provide flexible, fast and reliable protection of transmission and sub-transmission lines. They include full scheme 6-zone distance, plus aided directional earth fault (DEF) and comprehensive backup protection for utility lines and cables at all voltage levels, particularly oriented towards transmission grids.

MiCOM Agile P441, P442 & P444

Distance Protection Relays

Part of the MiCOM P40 platform, the Agile P441, P442 and P444 numerical full scheme distance relays provide flexible, fast and reliable protection of transmission and sub-transmission lines. They include full scheme 6-zone distance, plus aided directional earth fault (DEF) and comprehensive backup protection for utility lines and cables at all voltage levels, particularly oriented towards transmission grids.

What's New

Enhanced Ethernet board module with switchable Ethernet redundancy delivered in a single model. The new board module is supported on P442 and P444, also delivered along with the NERC CIP v6 Cybersecurity release, software 91.
It supports PRP, HSR and RSTP in one model, allowing a single P40 model to be used in any application requiring redundant Ethernet communications.
The new module is designed to handle high density traffic in the IEC 61850-8-1 network, with time latency halved. Larger architecture digital substations can also be supported, with up to 50 nodes now possible in IEC 62439 HSR rings.

Key Features & Benefits:
  • Universal IRIG-B – Modulated and demodulated supported in the same model
  • HSR Ring – Extended to 50 node support for larger substation architectures
  • Fast performance, particularly in onerous applications such as where process bus GOOSE is used for tripping purposes
  • NERC CIP cybersecurity including role-based access control (RBAC), RADIUS and SysLog

Overview

The Agile P441, P442 and P444 have a settable quadrilateral operating characteristic that offers consistent 0.85-1.1 cycle zone 1 operating time for general distance application. Customers have a choice of cost-effective built-in teleprotection with InterMiCOM, to implement permissive, blocking and intertripping schemes.
The IEC 61850 redundant Ethernet option offers RSTP and IEC 62439 PRP/HSR – with the HSR support extending for up to 50 nodes in a station bus ring.

Key benefits:
  • Comprehensive communication options including IEC 61850 and redundant Ethernet ports
  • IEC61850-9-2 interface option allows integration within digital substation process bus architectures
  • Unparallelled speed, security and selectivity
  • User customisable with graphical tools
Functional Block Diagram
Functional block diagram
ANSI ® Device Numbers and Functions
Device NumberFunction
25Check Synchronising
27Phase and Line Undervoltage
37Undercurrent
46Negative Sequence Overcurrent
49Thermal Overload
50Phase Definitive Time Overcurrent
51Phase Inverse-Time Overcurrent
52Circuit Breaker Control
59Phase and Line Overvoltage
67Directional Phase Overcurrent
68Power Swing Blocking
Device NumberFunction
79Autoreclose
85InterMiCOM Teleprotection
86Latching/Lockout Contacts
21BLLoad Encroachment/Blinder
21FLFault Locator
21FGGround Distance
21PPhase Distance
32NDirectional Zero-Sequence Power
46BCBroken Conductor
50/27Switch-on to Fault
50BFCB Failure
Device NumberFunction
50NEarth Fault Definite Time Overcurrent
50STStub Bus Protection
51FFVT Fail Overcurrent
51NNeutral/Ground IDMT Overcurrent
67NDirectional Neutral/Ground Overcurrent
81OOverfrequency
81UUnderfrequency
CTSCT Supervision
CVTSCapacitor VT Supervision
TCSTrip Circuit Supervision
VTSVT Supervision

Models

Manufacturing for P441 has been discontinued. As an alternative, please refer to P44 or P444.

P442 Line-Distance Management IED

The P442 is under last-time buy. Orders may be placed until 3rd March 2027 and will be fulfilled based upon availability. As an alternative, please refer to P44 or P444.
Buy Now

P444 Line-Distance Management IED for Transmission
Buy Now

MiCOM S1 Agile

Key benefits:
  • Powerful, free of charge, PC toolsuite
  • Optimum management of the installed base, structured as per the substation topology
  • Intuitive and versatile interface with file management facilities
  • Logical structure based on substation, voltage level and bay
  • Version control and cross-checking facilities for IED settings
  • Real-time measurement visualization – MiCOM S1 Agile extends to all MiCOM Agile IEDs - including P847 PMU and busbar schemes
Engineering Tool Suite

S1 Agile is the truly universal PC tool for MiCOM Agile relay, assemble all tools in a palette for simple entry, with intuitive navigation via fewer mouse-clicks. No-longer are separate tools required for redundant Ethernet configuration, phasor measurement unit commissioning, busbar scheme operational dashboards, programmable curve profiles or automatic disturbance record extraction – applications are embedded. MiCOM S1 Agile supports all existing MiCOM, K-Series and Modulex, including a utility for automatic conversion of setting files from previous generations of numerical relays like K-series and MiCOM P20 to the latest P40 Agile models.

To move to the future, with no loss of functionality, no loss of device support, and full compatibility with your installed base and system architecture – request a copy of S1 Agile with the contact form link below.

micom-screen
Key features in the MiCOM S1 family:
  • GE Vernova\’s integrated engineering tool that provides users with access to automation IED configuration and record data
  • Integrated configuration and monitoring features
  • Send and extract setting files
  • Event and disturbance record extraction and analysis
MiCOM S1 Agile software request

To receive the MiCOM S1 Agile, please use our Contact form. This will also ensure that you are kept up-to-date with the latest enhancements, including updates and bug fixes.

Refurbishment Solutions – “If It’s Blue Think to Renew”

GE Vernova\’s latest MiCOM P440 series models P441 to P444 inclusive offer an ideal path to refurbish an older installed base of MiCOM P440 relays. Whether those older products were initially sold as GE VERNOVA or AREVA-branded products, newer models retain pin-pin refurbishment capability. Advantageously, users can benefit from the advancements made in protection, control, communications, hardware and cybersecurity that have taken place in the intervening years. The new P40 retains form, fit and function compatibility but delivers the latest platform and software ready for today\’s environment, and for future-proofed application for the decades ahead.

Pin-Pin Upgrade Methodology:
  • Take the order code (CORTEC) of the older relay being removed, typically a blue case relay
  • Translate to today\’s latest GE Vernova MiCOM model, adding Ethernet options if required
  • Order the new P40 relay
  • Extract settings and logic, use S1 Agile toolsuite to convert settings
  • Detach the terminal blocks from old relay, leaving wiring attached / detach terminal blocks from the new.
  • Carefully examine the terminal blocks to see that no physical damage has occurred since installation
  • Mount new relay. Old relay blocks fit straight onto the new relay - safer, less wiring to reconnect.
  • It is recommended to apply rated current and voltage to the relay CT/VT inputs during secondary injection testing to check the continuity of the CT/VT terminal block connections to the relay.
  • Download converted files
  • Test, return circuit to service with only minutes of downtime

The MiCOM P54A/B/C/E range is designed for overhead line and cable applications up to 6 terminals, interfacing readily with the longitudinal (end-to-end) communications channel between line terminals. Previously, transmission and distribution circuits would have two or three ends only, whereas five or more ends are becoming common to connect renewable generation. All models are ready for protection topologies ranging from two to six terminals, whether those multi-terminals exist now, or are provisioned for connection in the future.

MiCOM Agile P54A, P54B, P54C & P54E

Multi-ended Line Differential Protection Systems

The MiCOM P54A/B/C/E range is designed for overhead line and cable applications up to 6 terminals, interfacing readily with the longitudinal (end-to-end) communications channel between line terminals. Previously, transmission and distribution circuits would have two or three ends only, whereas five or more ends are becoming common to connect renewable generation. All models are ready for protection topologies ranging from two to six terminals, whether those multi-terminals exist now, or are provisioned for connection in the future.

What's New

Protect lines with up to 6 terminals

For more than 100 years, electric power plants have mainly been large, utility-owned facilities, feeding distributed load based on unidirectional power flow. Over the past 20 years, smaller, independent power generation plants have been developed and distributed within electrical networks. The increasing number of Distributed Generation (DG) sites, and their increasing power ratings from kW to hundreds of MW, create new challenges for network planning and operation.

Distributed Generation Tee Infeeds to Existing Transmission Lines

Circuits near the coast may be candidates for tee infeeds to evacuate renewable energy from onshore and offshore wind generation. A tee infeed to a nearby transmission line can be a more cost effective solution to connect the generation to the grid than building a new substation. This economy enables more Distributed Generation connections to penetrate the network helping to meet green energy connection targets and reduce greenhouse gas emissions.

Multi-Ended Circuit Differential Lines

Previously transmission and distribution circuits would have two or three ends only. However, five or more ends are becoming common because large Distributed Generation sites such as onshore or offshore windfarms and solar farms are being connected to the grid. As the power networks evolve to transport power in ever more complex ring and meshed networks, line/cable differential protection becomes increasingly attractive, with its inherent ability to address grading/selectivity challenges and is scalable for multi-terminal circuits able to accommodate many connections of distributed generation along the line. GE Vernova’s Grid Solutions’ multi-ended current differential protection is now ready for any protection topology from two to six terminals, whether those multi-terminals exist now, or are provisioned for connection in the future.

Functional Block Diagram

p54abce

ANSI ® Device Numbers and Functions

Device NumberFunction
25Check Synchronising
27Phase and Line Undervoltage
46Negative Sequence Overcurrent
49Thermal Overload
50Phase Definitive Time Overcurrent
51Phase Inverse-Time Overcurrent
52Circuit Breaker Control
59Phase and Line Overvoltage
67Directional Phase Overcurrent
79Autoreclose
Device NumberFunction
85Teleprotection Channel Schemes
86Latching/Lockout Contacts
87Line Differential- 2 to 6 Ends
21FLFault Locator
46BCBroken Conductor
49SRSilicon Rectifier Thermal
50BFCB Failure
50NEarth Fault Definitive Time Overcurrent
51NNeutral/Ground IDMT Overcurrent
59NNeutral Voltage Displacement
59RRemote End Overvoltage
Device NumberFunction
64NRestricted Earth Fault
67NDirectional Neutral/Ground Overcurrent
81df/dtRate of Change Frequency
81OOverfrequency
81UUnderfrequency
81VUndervoltage Blocking
CTSCT Supervision
PSLProgrammable Logic
SEFSensitive Earth Fault
TCSTrip Circuit Supervision
VTSVT Supervision

Key Features

  • Powerful graphical Programmable Scheme Logic (PSL) customise relay logic
  • Real-time monitoring of remote, local and differential per-phase currents
  • Oscillography - 48 samples/cycle, up to 10.5 seconds record length
  • Event Recorder - 1024 time tagged events, time tagged to a resolution of 1 ms
Programmable Scheme Logic

Powerful graphical logic allows the user to customise the protection and control functions. The logic includes 32 timers, gates (OR, AND, MAJORITY) and set/reset latch functions, with the ability to invert the inputs and outputs and provide feedback.

The system is optimised to ensure that the protection outputs are not delayed by PSL operation.  The programmable scheme logic is configured using the graphical S1 Agile software. The relay outputs may be configured as latching (lockout) or self-reset. All aspects of MiCOM P40 IED configuration are managed using the S1 Agile software.

scheme-logic
Measurement and Recording Facilities

All events, fault and disturbance records are time tagged to a resolution of 1 ms. An optional IRIG-B port is available for accurate time synchronisation.

Power System Measurements

Instantaneous and time integrated voltage, current and power measurements are provided. These may be viewed in primary, or secondary values.

Fault Location

A fault location algorithm provides distance to fault in miles, kilometres, ohms or percentage of the line length. The proven algorithm employed tolerates pre-fault loading and fault arc resistance.

Event Records

Up to 1024 time-tagged event records can be stored. An optional modulated or demodulated IRIG-B port is available for accurate time synchronisation.

fault Records

The last 15 fault records are stored.

Disturbance Records

The oscillography has 16 analogue channels, 64 digital and 1 time channel, all at a resolution of 48 samples/cycle.

Key Features

  • Advanced IEC61850 Edition 2 implementation with complete settings via SCL files
  • Embedded IEEE 1588 time synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Redundant communications with zero downtime using optional PRP/HSR protocols
  • Wide range of supported protocols Courier/K-Bus, IEC 60870-5-103, DNP 3.0 (EAI-485 or Ethernet) and IEC 61850
Protection Communications Interfacing

To ensure compatibility with standard communications equipment, the MiCOM P54x Agile multi-ended line differential series is designed to work with IEEE C37.94TM. A direct fibre optic connection to a MUX is possible if the MUX is IEEE C37.94TM compliant.

In direct fibre optic applications, 1300 nm and 1550 nm channel options are available. The transmitters are designed with a large "optical budget" to support up to 150 km.

Communications Supervision

Dependable communications are essential for high-performance differential protection. Each active longitudinal channel is independently monitored and reports error statistics in line with guidance from ITU-T G.821.

Multi-ended line differential works in a ring connection, which provide comms redundancy. In the event of degraded communications, the ring communications channels will continue to provide protection, thus providing duplicated links via diverse communications paths.

Alternatively, back-up overcurrent elements can be switched into service, either as permanent parallel main protection, or temporary protection only during channel outages.

Communications supervisor flow diagram

Communications with Remote Operators and Substation Automation

Rear Scada Communication

The wide range of communications options, including IEC 61850, provides interfacing with almost any type of substation automation system or SCADA system.

The following protocols are available:

  • Courier/K-Bus
  • IEC 60870-5-103
  • DNP 3.0 (EAI-485 or Ethernet)
  • IEC 61850 Edition 2

P54x devices can be enhanced with an optional redundant Ethernet board. The redundancy is managed by the market's fastest recovery time protocols: IEC 62439-3 PRP and HSR allowing bumpless redundancy and RSTP, offering multi-vendor interoperability. The redundant Ethernet board supports either modulated or demodulated IRIG-B and the SNTP protocol for time synchronisation. The redundant Ethernet board also has a watchdog relay contact to alarm in case of a failure.

Second Rear Courier Port

An additional second rear port can be ordered as an option, designed typically for dial-up modem access by protection engineers/operators when the main port is reserved for SCADA traffic. This port also offers the option of -103 communications when IEC 61850 is the chosen first port protocol.

MiCOM S1 Agile

Key benefits:
  • Powerful, free of charge, PC toolsuite
  • Optimum management of the installed base, structured as per the substation topology
  • Intuitive and versatile interface with file management facilities
  • Logical structure based on substation, voltage level and bay
  • Version control and cross-checking facilities for IED settings
  • Real-time measurement visualization – MiCOM S1 Agile extends to all MiCOM Agile IEDs - including P847 PMU and busbar schemes
Engineering Tool Suite

S1 Agile is the truly universal PC tool for MiCOM Agile relay, assemble all tools in a palette for simple entry, with intuitive navigation via fewer mouse-clicks. No-longer are separate tools required for redundant Ethernet configuration, phasor measurement unit commissioning, busbar scheme operational dashboards, programmable curve profiles or automatic disturbance record extraction – applications are embedded. MiCOM S1 Agile supports all existing MiCOM, K-Series and Modulex, including a utility for automatic conversion of setting files from previous generations of numerical relays like K-series and MiCOM P20 to the latest P40 Agile models.

To move to the future, with no loss of functionality, no loss of device support, and full compatibility with your installed base and system architecture – request a copy of S1 Agile with the contact form link below.

Key features in the MiCOM S1 family:
  • GE Vernova’s integrated engineering tool that provides users with access to automation IED configuration and record data
  • Integrated configuration and monitoring features
  • Send and extract setting files
  • Event and disturbance record extraction and analysis
MiCOM S1 Agile software request

To receive the MiCOM S1 Agile, please use our Contact form. This will also ensure that you are kept up-to-date with the latest enhancements, including updates and bug fixes.

Models

P54A compact (40TE), economical line differential protection without VT inputs, offering non-directional backup protection.

P54B compact (40TE), economical line differential protection with directionalised back-up protection and inbuilt reclosing and check synchronism.

P54C transmission-class 1/3-pole tripping line differential protection with backup protection and inbuilt reclosing and check synchronism (built from today’s P543 hardware).

P54E transmission-class 1/3-pole tripping line differential protection with back-up protection and inbuilt reclosing and check synchronism with a large number of binary I/O for traditional hardwired schemes (built from P545 hardware).

New and Enhanced Communication Capabilities
  • New process bus module supports IEC 61869 sample values, PTP master capabilities and SV switching (FW 7.9x)
  • New UR process bus modules supporting IEC61850-9-2LE Merging Units and IEC61850-9-2 Hardfiber (FW 7.8x) Module Training available here
  • Support switchable IEC 61850 Ed. 1 and Ed. 2 and redundant SNTP (FW 7.7x)
  • New UR front panel with integrated 7” color, graphical display - providing operators with enhanced situational awareness (FW 7.6x)
  • High density I/O module supporting up to 120 inputs or up to 72 contact outputs – eliminating the need for additional discrete devices (FW 7.6x)
Cyber Security - CyberSentry UR (FW v7.xx)

CyberSentryTM enables UR devices to deliver full cyber security features that help customers to comply with cyber security requirements (NERC CIP, IEEE 1686, IEC 62443, etc):

  • Secured firmware upgrade: FW file includes hash code that enables authentication prior to being used for upgrading UR Relay (FW 7.9x)
Fully Compatible with IEC 61850-9-2LE or IEC61869 process bus schemes:
  • Can connect to up to 8 merging units over -9-2LE or 61869
  • Supports PRP, HSR, dual HSR and point-to-point process bus topology
  • Provides support for GE Vernova’s IEC 61850 HardFiber Process Bus Solution
Extended Oscillography Records (FW v7.xx)
  • Increased number of digital and analog channels (FW 7.90)
  • Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE 2013 standard (FW v7.40)
  • Configurable events allow for records of up to 45s at 64 samples per cycle
New and Enhanced Protection and Control Functionality
  • 6-distance zones and sub-cycle performance SW options (FW 8.0)
  • New TGFD and Inrush detection elements (FW 8.0)
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)

Key Features

  • Phase-segregated line current differential with adaptive restraint and ground differential, stub bus protection
  • In-zone power transformer enables savings on CTs and protection device requirements
  • Thermal protection, under/over frequency, broken conductor
  • Phase distance (five zones) with independent compensation settings for in-zone power transformers

 

  • Ground distance (five zones) with independent self and mutual zero- sequence compensation, reverse power
  • Sub-cycle distance performance available
  • Line pickup, reverse power, out-of-step tripping and power swing blocking
  • Thermal overload, phase, neutral and negative sequence directional overcurrent, TGFD, broken conductor and more
  • Over, under and rate of change of frequency, synchronism check for dual-breaker applications

Protection & Control

The L90 is a high-end cost-effective line current differential protection relay intended for transmission lines and cables of different voltage levels, providing reliable and secure operation even under worst case power system conditions. The L90 provides high-speed phase-segregated fault clearance suitable for single and three-pole tripping applications. Part of the Universal Relay family, the L90 comes with a variety of versatile features, truly integrating protection, monitoring, metering, communication and control in one easy-to-use device. The Universal Relay family offers a high degree of modularity in its design and functionality, providing superior performance in protection and control, while meeting the toughest requirements of the marketplace.

Functional Block Diagram
ANSI® Device Numbers & Functions
Device NumberFunction
21GGround Distance
21PPhase Distance
24Synchronism Check
25Synchrocheck
27PPhase Undervoltage
27XAuxiliary Undervoltage
32Sensitive Directional Power
49Thermal Overload
50BFBreaker Failure
50DDCurrent Disturbance Detector
50GGround Instantaneous Overcurrent
50NNeutral Instantaneous Overcurrent
Device NumberFunction
50PPhase Instantaneous Overcurrent
50_2Negative Sequence Instantaneous Overcurrent
51GGround Time Overcurrent
51NNeutral Time Overcurrent
51PPhase Time Overcurrent
51_2Negative Sequence Time Overcurrent
52AC Circuit Breaker
59NNeutral Overvoltage
59PPhase Overvoltage
59XAuxiliary Overvoltage
Device NumberFunction
67_2Negative Sequence Directional Overcurrent
67NNeutral Directional Overcurrent
67PPhase Directional Overcurrent
68Power Swing Blocking
78Out-of-Step Tripping
79Automatic Recloser
81U/OUnder/Over Frequency, df/dt
87LSegregated Line Current Differential
81ROCOFRate of Change of Frequency
87LGGround Line Current Differential

Key Features

  • Real-time monitoring of remote, local and differential per-phase currents
  • Oscillography - 64 samples/cycle, up to 64 records
  • Event Recorder - 1024 time tagged events, with 0.5ms scan of digital inputs
  • Data Logger - Up to 16 channels with user selectable sampling rate
  • P & M class synchrophasors of voltage, current and sequence components - 1 to 120 frames/sec
  • Multi-ended fault location consistently providing 2% accuracy
Monitoring & Diagnostics
The L90 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
Advanced Automation

The L90 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average line relay. The L90 integrates seamlessly with other UR relays for complete system protection.

FlexLogic allows for the customization of the L90 to operate and control the breakers and other auxiliary devices needed to fit most line protection schemes and applications.

Key Features

Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P & C life cycle costs

  • Three independent 100Mbps Ethernet ports enable purpose specific LAN support that eliminates latency effect of heavy traffic protocols on mission critical communication services
  • Embedded IEEE 1588 time-synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Direct I/O secures high-speed exchange of binary data between URs
  • Increase network availability by reducing failover time to zero through IEC62439-3 PRP, HSR or dual HSR support
Advanced Communications

The L90 provides for secure remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available three independent and redundant Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner.

The L90 supports the most popular industry standard protocols enabling easy, direct integration into monitoring and SCADA systems.

  • IEC 61850-9-2LE/IEC 61869 networked or IEC61850-9-2 Hardfiber process bus support
  • DNP 3.0 (serial & TCP/IP)
  • IEC 60870-5-103 and IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  • HTTP, TFTP, SFTP and MMS file transfer
  • Redundant SNTP and IEEE 1588 for time synchronization
  • PRP as per IEC 62439-3
  • IRC module that combines C37.92 multimode and direct connection singlemode
  • Supports Routable GOOSE (R-GOOSE)
Interoperability with Embedded IEC 61850

Use the L90 with integrated IEC 61850 to lower costs associated with line differential protection, control and automation. GE Vernova’s leadership in IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.

The L90’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. 
Learn more

The L90 can also connect to GE Vernova MU320 or third-party merging units using standard IEC 61869 or IEC 61850-9-2LE communication protocols.

Cyber Security - CyberSentry™ UR (FW v7.4xx)

CyberSentry enables UR devices to deliver full cyber security features that help customers to comply with NERC CIP and NITIR 7628 cyber security requirements through supporting the following core features:

Secure FW upgrade

UR FW files v7.9 and up now include a hash code that allows for authentication prior to being used for upgrading UR devices.

Password Complexity

Supporting up to 20 alpha- numeric or special characters, UR passwords exceed NERC CIP requirements for password complexity. Individual passwords per role are available.

AAA Server Support (Radius)

Enables integration with centrally managed authentication and accounting of all user activities and uses modern industry best practices and standards that meet and exceed NERC CIP requirements for authentication and password management.

Role Based Access Control (RBAC)

Efficiently administrate users and roles within UR devices. The new and advanced access functions allow users to configure up to five roles for up to eight configurable users with independent passwords. The standard “Remote Authentication Dial In User Service” (Radius) is used for authentication.

Event Recorder (Syslog for SEM)

Capture all cyber security related events within a SOE element (login, logout, invalid password attempts, remote/local access, user in session, settings change, FW update, etc), and then serve and classify data by security level using standard Syslog data format. This enables UR devices integration with established SEM (Security Event Management) systems.

EnerVista™ Software

The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the L90 relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the L90 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. 
Learn More

The T60 is designed for various power applications, including autotransformers, generator step-up transformers, split-phase, angle regulating transformers and reactors. It uses multiple current and voltage inputs to provide primary protection and backup protection of transformers, including differential, ground differential, five distance zones, phase, neutral, and ground overcurrent, under and overvoltage, under and overfrequency, over-fluxing, and breaker failure.

Multilin T60

Transformer Protection System

The T60 is designed for various power applications, including autotransformers, generator step-up transformers, split-phase, angle regulating transformers and reactors. It uses multiple current and voltage inputs to provide primary protection and backup protection of transformers, including differential, ground differential, five distance zones, phase, neutral, and ground overcurrent, under and overvoltage, under and overfrequency, over-fluxing, and breaker failure.

New and Enhanced Communication Capabilities

  • New process bus module supports IEC 61869 sample values, PTP master capabilities and SV switching (FW 7.9x)
  • New UR process bus modules supporting IEC61850-9-2LE Merging Units (FW 7.8x) Module Training available here
  • Support switchable IEC 61850 Ed. 1 and Ed. 2 and redundant SNTP (FW 7.7x)
  • New UR front panel with integrated 7” color, graphical display - providing operators with enhanced situational awareness (FW 7.6x)
  • High density I/O module supporting up to 120 inputs or up to 72 contact outputs – eliminating the need for additional discrete devices (FW 7.6x)

Cyber Security - CyberSentry UR (FW v7.xx)

CyberSentryTM enables UR devices to deliver full cyber security features that help customers to comply with cyber security requirements (NERC CIP, IEEE 1686, IEC 62443, etc):

  • Secured firmware upgrade: FW file includes hash code that enables authentication prior to being used for upgrading UR Relay (FW 7.9x)

Fully Compatible with IEC 61850-9-2LE or IEC61869 process bus schemes:

Can connect to up to 8 merging units over -9-2LE or 61869 Supports PRP, HSR, dual HSR and point-to-point process bus topology Provides support for GE Vernova’s IEC 61850 HardFiber Process Bus Solution

Extended Oscillography Records (FW v7.xx)

  • Increased number of digital and analog channels (FW 7.90)
  • Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE 2013 standard (FW v7.40)
  • Configurable events allow for records of up to 45s at 64 samples per cycle

T60 Protection System to Deliver Synchrophasor Capabilities (FW version 5.90)

New and Enhanced Protection and Control Functionality

  • Inter-turn transformer and dedicated Harmonic/Inrush detection elements (FW 8.0)
  • • CT exclusion setting (FW 7.8)
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)

New RRTD and RTD Alarm and Trip Settings

The T60 offers RTD alarm and trip settings to provide advanced monitoring of power transformers’ temperature. In addition, the RRTD module enables remote monitoring and metering of up to 12 programmable RTDs which reduces the number of RTD cables and provides temperature backup protection (firmware version 5.70). Learn More

Key Benefits

  • Dual-slope, dual-breakpoint differential restraint characteristic, restrained and unrestrained differential, inter-turn fault detection
  • 2nd harmonic inrush, overexcitation inhibit plus independent harmonic detection element
  • Transformer overexcitation protection
  • Restricted ground fault
  • Loss-of-life, aging factor, hottest spot
  • Five zones backup distance protection with power swing detection and load encroachment function
  • Synchrocheck, ROCOF, over and under frequency
Protection & Control

The T60 transformer protection system is a comprehensive three-phase transformer relay designed to protect medium and large power transformers. The T60 provides automatic or user-definable magnitude reference winding selections for CT ratio matching, and performs automatic phase shift compensation for all types of transformer winding connections. The T60 algorithm allows the user to enable removal of the zero-sequence current even for delta-connected transformer windings, facilitating transformers with a variety of grounding configurations. As part of the Universal Relay (UR) Family, the T60 provides superior protection and control.

Functional Block Diagram

Protection & Control

ANSI Device Numbers & Functions

Device NumberFunction
21PPhase Distance
21GGround Distance
24Volts Per Hertz
25Synchrocheck
27PPhase Undervoltage
27XAuxiliary Undervoltage
49Thermal Overload
50BFBreaker Failure
50GGround Instantaneous Overcurrent
50NNeutral Instantaneous Overcurrent
Device NumberFunction
50PPhase Instantaneous Overcurrent
50/87Instantaneous Differential Overcurrent
51GGround Time Overcurrent
51NNeutral Time Overcurrent
51PPhase Time Overcurrent
59NNeutral Overvoltage
59PPhase Overvoltage
59XAuxiliary Overvoltage
Device NumberFunction
67NNeutral Directional Overcurrent
67PPhase Directional Overcurrent
68Power Swing Blocking
78Out-of-Step Tripping
81OOverfrequency
81UUnderfrequency
81RRate of Change of Frequency (ROCOF)
87GRestricted Ground Fault
87TTransformer Differential

Key Features

  • Metering - current, voltage, power, energy, frequency, temperature, transformer monitoring
  • P & M class synchrophasors of voltage, current and sequence components – 1 to 120 frames/sec
  • Oscillography – analog and digital parameters at 64 samples/cycle
  • Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs
  • Data Logger - 16 channels with sampling rate up to 1 sample / cycle
  • Setting for security audit trails for tracking changes to T60 configurations
 

Monitoring & Diagnostic

The T60 includes high accuracy metering and recording for all AC signals. Voltage, current, and power metering are built into the relay as a standard feature. Current and voltage parameters are available as total RMS magnitude, and as fundamental frequency magnitude and angle. For power quality applcations, harmonic measurements (up to the 25th) for voltage and current are available. T60 can monitor, calculate and log hottest-spot temperature, aging factor and loss-of-life data over a long period. This data, combined with economic analysis, allows criteria to be developed regarding the best time at which to replace a power transformer due to load growth, i.e. to minimize the cost without significantly increasing the risk.

Monitoring & Diagnostic The B30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring.
Advanced Automation

The T60 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average transformer relay. The T60 integrates seamlessly with other UR relays for complete system protection.

FlexLogic™ diagram FlexLogic™ allows for the customization of the T60 to operate and control the breakers and other auxiliary devices needed to fit most generator protection schemes and applications.

Key Features

Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P & C life cycle costs

  • Three independent 100Mbps Ethernet ports enable purpose specific LAN support that eliminates latency effect of heavy traffic protocols on mission critical communication services
  • Embedded IEEE 1588 time-synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Direct I/O secures high-speed exchange of binary data between URs
  • Increase network availability by reducing failover time to zero through IEC62439-3 PRP, HSR or dual HSR support

Advanced Communications

The T60 provides advanced communications technologies for remote data and engineering access, making it the most advanced and flexible transformer protection relay to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available three independent and redundant Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner. 
The T60 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems.

  • IEC 61850-9-2LE/IEC 61869 networked or IEC61850-9-2 Hardfiber process bus support
  • DNP 3.0 (serial & TCP/IP)
  • Ethernet Global Data (EGD)
  • IEC 60870-5-103 and IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  • HTTP, TFTP, SFTP and MMS file transfer
  • Redundant SNTP and IEEE 1588 for time synchronization
  • PRP as per IEC 62439-3
  • Supports Routable GOOSE (R-GOOSE)
Interoperability with Embedded IEC 61850

Use the T60 with integrated IEC 61850 to lower costs associated with power transformer, control and automation. GE Vernova’s leadership in IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.

HardFiber System

The T60’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. Learn more

The T60 can also connect to GE Vernova MU320 or third-party merging units using standard IEC 61869 or IEC 61850-9-2LE communication protocols.

Cyber Security - CyberSentry™ UR (FW v7.4xx)

CyberSentry enables UR devices to deliver full cyber security features that help customers to comply with NERC CIP and NITIR 7628 cyber security requirements through supporting the following core features:

Secure FW upgrade

UR FW files v7.9 and up now include a hash code that allows for authentication prior to being used for upgrading UR devices.

Password Complexity

Supporting up to 20 alpha- numeric or special characters, UR passwords exceed NERC CIP requirements for password complexity. Individual passwords per role are available.

AAA Server Support (Radius)

Enables integration with centrally managed authentication and accounting of all user activities and uses modern industry best practices and standards that meet and exceed NERC CIP requirements for authentication and password management.

Role Based Access Control (RBAC)

Efficiently administrate users and roles within UR devices. The new and advanced access functions allow users to configure up to five roles for up to eight configurable users with independent passwords. The standard “Remote Authentication Dial In User Service” (Radius) is used for authentication. 

Event Recorder (Syslog for SEM)

Capture all cyber security related events within a SOE element (login, logout, invalid password attempts, remote/local access, user in session, settings change, FW update, etc), and then serve and classify data by security level using standard Syslog data format. This enables UR devices integration with established SEM (Security Event Management) systems.

EnerVista™ Software

The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the T60 relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the T60 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. Learn More

Enervista Software

RT431 Time Code Generator is a compact GPS-based clock designed to be installed on a DIN rail that supports the Precise Time Protocol (IEEE 1588 PTP) version 2. PTP provides accurate synchronization over Ethernet networks within 100 ns accuracy, enabling applications like synchrophasors without the need to use separate IRIG-B and PPS networks. RT431 configured as PTP slave also works as a transceiver from PTP to IRIG-B, serial or pulse time codes, enabling the use of PTP on IEDs that do not support this protocol.

Reason RT431

GPS Precision-Time Clock

RT431 Time Code Generator is a compact GPS-based clock designed to be installed on a DIN rail that supports the Precise Time Protocol (IEEE 1588 PTP) version 2. PTP provides accurate synchronization over Ethernet networks within 100 ns accuracy, enabling applications like synchrophasors without the need to use separate IRIG-B and PPS networks. RT431 configured as PTP slave also works as a transceiver from PTP to IRIG-B, serial or pulse time codes, enabling the use of PTP on IEDs that do not support this protocol.

The demand for accurate time synchronization available 24/7 increases with the growth of critical substation applications, such as phasor measurement, merging units, traveling-wave fault location and current differential protection operating over SONET and MPLS systems. In order to yield the best accuracy and granularity from such applications, the use of a common, precision-time reference is essential.

Reason RT430

GNSS Precision-Time Clocks

The demand for accurate time synchronization available 24/7 increases with the growth of critical substation applications, such as phasor measurement, merging units, traveling-wave fault location and current differential protection operating over SONET and MPLS systems. In order to yield the best accuracy and granularity from such applications, the use of a common, precision-time reference is essential.