Compact switchgear

GE’s Compact Air-Insulated Breaker Assembly (CABA) is a modular, compact switchgear system combining a live tank circuit breaker, double sided disconnect switch and other AIS equipment mounted on a common frame. It can be installed in greenfield substations or retrofit into an existing substation. CABA can be installed on existing foundations and is designed for space savings due to its compactness.

This flexible, compact breaker assembly is well suited for a variety of applications including transformer protection, line and cable switching, capacitor bank and back-to-back switching, reactor switching and circuit switching.

Compact Switchgear

Compact Air-Insulated Breaker Assembly CABA

Compact switchgear

GE’s Compact Air-Insulated Breaker Assembly (CABA) is a modular, compact switchgear system combining a live tank circuit breaker, double sided disconnect switch and other AIS equipment mounted on a common frame. It can be installed in greenfield substations or retrofit into an existing substation. CABA can be installed on existing foundations and is designed for space savings due to its compactness.

This flexible, compact breaker assembly is well suited for a variety of applications including transformer protection, line and cable switching, capacitor bank and back-to-back switching, reactor switching and circuit switching.

GE Advantage

CABA leverages GE’s expertise in high voltage equipment, including circuit breakers and disconnect switches, to provide a reliable substation solution. GE has more than 100,00 circuit breakers with spring-spring operating mechanisms in service throughout the world.

Key Features

  • Complete factory assembly allows CABA to easily replace existing equipment for a high quality solution with reduced delivery time
  • Ideal for replacement or upgrade of circuit switcher installations providing full circuit breaker function in the same space
  • Reliable spring-spring operating mechanisms
  • Meets the requirements of IEC and IEEE/ANSI standards

Key Benefits

  • Modular design for green field or retrofit installations
  • Improved substation protection
  • No new foundations needed for retrofits with standardized modules
  • Easy installation and commissioning
  • Circuit breaker performance in a circuit switcher footprint
 

Specifications

Live Tank circuit breaker

Rated voltagekV72.5145245245
Circuit breaker type GL 309GL 312GL 314GL 314X
Circuit-breaker operating mechanism FK3-1 SpringFK3-1 SpringFK3-6 SpringFK3-4 Spring
Rated continuous currentA3,1503,1503,1503,150
Rated frequencyHz50/6050/6050/6050/60
Rated dielectric withstand     
- Power frequency 1 minute drykArms160310460460
- BIL (1.2/50s impulse wave)kVpeak3506509001,050
- 2s chopped wave kVpeakkVpeak4528381,1601,160
Rated short-circuit breaking capacity     
- Perioduc componentkArms40404063
- percentage DC component%53535368
- First pole to clear 1,51,51,51,5
- Interrupting time cycles 3333
- Rated short-circuit making currentkApeak108108108170
- Rate out-of-phase breaking capacity kAkA10101016
Rated line-charger breaking capacity (C2 Class)A100160400400
Rated capacitor bank breaking capacity (C2 Class)A6304001,2001,200
Rated operating sequence  o-0,3-CO-15s-CO  
Ambient temperature (without blanet heaters)oC    
* Low temperature performerce to -50oC is available with the used of mixed gas (SF6/CF4)

Three phase disconnector - double side break

Rated voltagekV72.5145245245
Disconnect switch type S3CDS3CDS3CDS3CD
Disconnect switch operating mechanism Manual handcrank*Manual handcrank*Manual handcrank*Manual handcrank*
Rated frequencyHz50/6050/6050/6050/60
Rated continuous currentA3,1503,1503,1503,150
Rated continuous current 30 minutes emergency 4100A4,1004,1004,1004,100
Rated dielectric withstand (IEEE/ANSI Standard)     
- Power frequency 1 minute drykV175335465465
- Power frequency 10 second wetkV146275385385
- BIL (1.2x50 per second rated withstand)kVpeak3506509001,050
Rated short time current     
- Three (3) secondkArms63634063
- Momentary currentkA100100100100
- Peak currentkApeak164164164164
- Capacitance current switching capabilityA1111
- Transformer magnetising current switching capabilityA3333
Open gap length (IEEE/ANDI standard)Inch22x238x250x250x2
Open rotation gapDegrees80808080
Rated ice breaking capabilityInch0.750.750.750.75
Ambient temperature (without blanet heaters)oC-50 to +50-50 to +50-50 to +50-50 to +50
* Motor mechanism on request
 

Drawings

CABA Drawing

CABA Dimensions

CABA Dimensions