GE's B65 GIS is a field-proven solution with high availability that meets the challenges of networks up to 145 kV, 40 kA, 3150 A for power generation, transmission, distribution, tertiary and heavy industry applications. The B65 is one of the most compact 145 kV GIS solutions with single-phase enclosures and is comprised of small, light components making it easy to handle.

The B65 is environmentally friendly and features one of the lowest gas weights on the market along with an advanced SF6 sealing system. Full digital monitoring control and protection capabilities enable smart grid integration.

Building on GE's GIS experience of more than 50 years, the B65 provides high availability and data reliability with single-phase enclosures to prevent phase-to-phase faults and pure-spring circuit breakers drives.

B65

Gas-Insulated Substations

GE's B65 GIS is a field-proven solution with high availability that meets the challenges of networks up to 145 kV, 40 kA, 3150 A for power generation, transmission, distribution, tertiary and heavy industry applications. The B65 is one of the most compact 145 kV GIS solutions with single-phase enclosures and is comprised of small, light components making it easy to handle.

The B65 is environmentally friendly and features one of the lowest gas weights on the market along with an advanced SF6 sealing system. Full digital monitoring control and protection capabilities enable smart grid integration.

Building on GE's GIS experience of more than 50 years, the B65 provides high availability and data reliability with single-phase enclosures to prevent phase-to-phase faults and pure-spring circuit breakers drives.

Customer Benefits

 

Customer Benefits


Main Characteristics

 

Environment friendliness

  • Low gas weight
  • Advanced SF6 sealing system

 

High availability

  • Highly reliable solutions backed by years of design and installation experience
  • Current transformers outside SF6
  • Single-phase enclosures: no phase-to-phase fault
  • Pure-spring circuit breaker drives

 Low costs of land and civil works

  • Most compact 145 kV GIS with single-phase enclosures

 

Shortest Site Works

  • Light and small single-phase components, easy to handle

 

Smart Grid Features

  • full-digital monitoring, control and protection

Specifications

General ratings
Reference electrotechnical standardsIEEE/IEC
Voltages145 kV
Withstand voltages 
- Short-duration power-frequency, phase-to-earth / across isolating distance275/315 kV
- Lightning impulse, phase-to-earth / across isolating distance650/750 kVp
Frequency50/60 Hz
Continuous currentup to 3150A
Short-time withstand current40 kA
Peak withstand current100/108 kAp
Duration of short-circuit3s
Installationindoor
Ambient temperature rangedown to -25 / up to +55 °C
Circuit-breaker ratings
First-pole-to-clear factor1.5
Short-circuit breaking current40 kA
Short-circuit making current100/108 kAp
Operating sequenceO-0.3s-CO-3 min-CO/CO-15s-CO
Drive type (three-phase or single-phase)Pure-spring
Breaking time50 ms
Closing time95 ms
Mechanical enduranceM2 class
Capacitive switchingC2 class
Disconnector and low-speed earthing switch ratings
Capacitive current switching0.1 A
Bus-transfer current switching capability1600 A / 10 V
Mechanical enduranceM2 class
Make-proof earthing switch ratings
Making current capability100/108 kAp
Switching capability - electromagnetic coupling80 A / 2 kV
Switching capability - electrostatic coupling2 A / 6 kV
Mechanical enduranceM1 class