GE's B105 GIS is a compact, field-proven solution with high availability that meets the challenges of networks up to 245 kV for power generation, transmission, distribution, tertiary and heavy industry applications. The B105 is available in several ratings:

  • 245 kV, 50/63 kA, 3150/4000 A

The B105 is environmentally friendly and features one of the lowest gas weights on the market along with an advanced SF6 sealing system. Full digital monitoring control and protection capabilities enable the B105 to be readily integrated into the smart grid.

B105

Gas-Insulated Substations up to 245 kV

GE's B105 GIS is a compact, field-proven solution with high availability that meets the challenges of networks up to 245 kV for power generation, transmission, distribution, tertiary and heavy industry applications. The B105 is available in several ratings:

  • 245 kV, 50/63 kA, 3150/4000 A

The B105 is environmentally friendly and features one of the lowest gas weights on the market along with an advanced SF6 sealing system. Full digital monitoring control and protection capabilities enable the B105 to be readily integrated into the smart grid.

Customer Benefits

 

Customer Benefits

 

 

 

 

Main Characteristics

Environment friendliness

  • Low gas weight
  • Advanced SF6 sealing system
  • Smart grid features including full-digital monitoring, control and protection

High availability

  • One of the best experiences and high data reliability
  • Current transformers outside SF6
  • Pure-spring circuit breaker drives
  • State-of-the-art maintenance isolating device: major repair and HV tests with no more than 1 bay down
  • Drives and accessories at easy reach

Low costs of land and civil works

  • One of the most compact GIS with single-phase enclosures only: bay footprint up to 50% below market average depending on kV rating
  • Complete bays assembled, wired, tested and shipped
  • Light and small single-phase components, easy to handle

Specifications

General ratings
Reference electrotechnical standardsIEC/IEEE/GB
Voltagesup to 245 kV
Withstand voltages 
- Short-duration power-frequency, phase-to-earth / across isolating distance460/530 kV
- Lightning impulse, phase-to-earth / across isolating distance1050/1200 kVp
Frequency50/60 Hz
Continuous current3150/4000 A
Short-time withstand current50/63 kA
Peak withstand current135/170 kAp
Duration of short-circuit3s
InstallationIndoor/outdoor
Ambient temperature rangedown to -25 / up to +55 °C
Circuit-breaker ratings
First-pole-to-clear factor1.3-1.5
Short-circuit breaking current50/63 kA
Short-circuit making current135/170 kAp
Operating sequenceO-0.3s-CO-3 min-CO/CO-15s-CO
Drive type (three-phase or single-phase)Pure-spring
Breaking time<50 ms
Closing time<100 ms
Mechanical enduranceM2 class
Capacitive switchingC2 class
Disconnector and low-speed earthing switch ratings
Capacitive current switching0.25 A
Bus-transfer current switching capability1600 A / 20 V
Mechanical enduranceM2 class
Make-proof earthing switch ratings
Making current capability135/170 kAp
Switching capability - electromagnetic coupling80 A / 2 kV
Switching capability - electrostatic coupling3 A / 12 kV
Mechanical enduranceM1 class