The CGVB-08 vertical break disconnector is available in a wide range of ratings and is a robust and reliable performer. The double jaw contact system provides low maintenance, long life and excellent electrical and mechanical performance in the most adverse operating conditions. The CGVB-08 can be customized for different layouts to meet specific project needs.

Customer Benefits
  • Reduced phase spacing requirements
  • Virtually maintenance free
  • No special tools required
  • Wide range of accessories available
  • Customizable to meet specific needs

CGVB-08

Vertical Break Disconnector up to 345 kV

The CGVB-08 vertical break disconnector is available in a wide range of ratings and is a robust and reliable performer. The double jaw contact system provides low maintenance, long life and excellent electrical and mechanical performance in the most adverse operating conditions. The CGVB-08 can be customized for different layouts to meet specific project needs.

Customer Benefits
  • Reduced phase spacing requirements
  • Virtually maintenance free
  • No special tools required
  • Wide range of accessories available
  • Customizable to meet specific needs

  • Up to 4000 A
  • Up to 80 kA/3 s
  • Temperatures from -50°C to +50°C
  • Ice up to 20 MM (3/4”)
  • Virtually maintenance free with factory-sealed bearings, life-time greased or self-lubricating parts and corrosion-free materials

Optionnal Devices

The CGVB-08 can be fitted with integrated grounding switches, mounted either parallel or perpendicular to the disconnect switch blade travel. In addition, it can be fitted to a wide range of accessories including high speed whips, silver inlaid contact, interlocking mechanisms and auxiliary contacts.

Specifications

25 to 245 kV 1200-2000 AMP

Rated VoltageMax. rated currentShort circuit currentBILA inch(mm)B inch(mm)C inch(mm)D inch(mm)E inch(mm)
25.8 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec15059 (1499)26 (656)63 (1603)14 (356)10 (254)
38 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec20069 (1753)30 (757)77 (1958)18 (457)10 (254)
72.5 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec35085 (2165)42 (1062)103 (2619)30 (762)10 (254)
121 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec550102 (2597)57 (1441)135 (3430)45 (1143)10 (254)
145 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec660113 (2876)66 (1670)155 (3938)54 (1372)10 (254)
169 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec750122 (3105)74 (1873)172 (4370)62 (1575)10 (254)
242 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec900147 (3734)93 (2364)218 (5527)80 (2032)11 (286)
242 kV1200-2000 A38 kA 3 sec - 63 kA 3 sec1000163 (4140)105 (2668)246 (6238)92 (2337)11 (286)
 


 

25 to 245 kV 3000-4000 AMP

Rated VoltageMax. rated currentShort circuit currentBILF inch(mm)G inch(mm)H inch(mm)J inch(mm)K inch(mm)
25.8 kV4000 A80 kA 3 sec15075 (1911)24 (621)87 (2211)15 (381)10 (254)
38 kV4000 A80 kA 3 sec20084 (2125)29 (730)101 (2556)18 (457)10 (254)
72.5 kV4000 A80 kA 3 sec35095 (2410)39 (1002)122 (3099)30 (762)10 (254)
121 kV4000 A80 kA 3 sec550113 (2877)54 (1383)160 (3937)45 (1143)10 (254)
145 kV4000 A80 kA 3 sec650124 (3156)63 (1611)175 (4445)54 (1372)10 (254)
169 kV4000 A80 kA 3 sec750131 (3334)71 (1814)190 (4826)62 (1575)10 (254)
242 kV4000 A80 kA 3 sec900135 (4172)89 (2272)243 (6153)80 (2032)10 (254)
242 kV4000 A80 kA 3 sec1050184 (4680)101 (2576)274 (6966)92 (2337)10 (254)
362 kV1200-4000 A80 kA 3 sec1300199 (5042)115 (2910)303 (7706)106 (2692)9 (230)

Drawings

Customized layouts available upong request. Phase-to-phase distance defined by substation layout.