DT1-38
Dead Tank Circuit Breaker for 38 kV
GE's DT series of dead tank circuit breakers are known for their advanced self-blast interrupters, leak resistant cast aluminum enclosures and durable low energy spring operated mechanisms. More than 100,000 GE circuit breakers with self-blast interrupters and FK spring-operated mechanisms have been in service since 1989.
The compact DT1-38 design can be used in new or retrofit applications. The 3-pole circuit breaker forms a complete, fully assembled, factory-tested, transportable unit. The on-site installation requires only a few simple steps. For installations where truck shipment is impossible, the DT1-38 can be readied for standard container shipment as a fully assembled unit.
DT1-38
Dead Tank Circuit Breaker for 38 kV
GE's DT series of dead tank circuit breakers are known for their advanced self-blast interrupters, leak resistant cast aluminum enclosures and durable low energy spring operated mechanisms. More than 100,000 GE circuit breakers with self-blast interrupters and FK spring-operated mechanisms have been in service since 1989.
The compact DT1-38 design can be used in new or retrofit applications. The 3-pole circuit breaker forms a complete, fully assembled, factory-tested, transportable unit. The on-site installation requires only a few simple steps. For installations where truck shipment is impossible, the DT1-38 can be readied for standard container shipment as a fully assembled unit.
Performance
Thanks to its robust design, the DT1-38 is a highly reliable circuit breaker even under the most severe operating conditions and is tested to meet or exceed IEEE/ANSI and IEC as C2 class for capacitance switching including back-to-back (low restrike probability) and reactor switching applications. Extensive mechanical operation design testing ensures trouble-free operation for the lifetime of the circuit breaker. Intensive production leak testing ensures superior in-service SF6 performance.
Quality components play a key role in the high performance of the unit. DT1-38 components include:
- Third-generation self-blast interrupter chamber
- Pressure relief system for passive protection of both substation and personnel
- Generous space for current transformers
- Field-proven, temperature-compensated density monitor with two-stage pressure switch and three-color dial
- DILO SF6 filling connection
- Galvanized steel base frame
- Reliable spring-spring-operated mechanism
GE designs, manufactures, tests and delivers its circuit breakers in accordance with IEEE/ANSI and IEC standards, maintaining a quality assurance system according to ISO-9001 and ISO-14001. The competence center for dead tank circuit breakers is located in Charleroi, PA (USA).
Specifications
IEEE/ANSI | IEC | Value | Units |
Rated maximum valtage | Rated voltage | 38 | kV |
Rated power frequency | Rated frequency | 50/60 | Hz |
Rated dielectric withstand capability: - dry withstand - wet withstand | Rated insulation level - at power frequency,dry - at power frequency,wet | 80 75 | kV kV |
Rated lightning impulse withstand voltage | - at lightning impulse | 200* | kV |
Rated chopped wave impulse voltage 2us | 258 | kV | |
Rated continuous current | Rated normal current | 1,200/2,000/3,000 | A |
Rated short-circuit current | Rated short-circuit breaking current | 40 | kA |
Rated closing,latching and short time carrying current | 104 | kA | |
Rated short-circuit making current | 100 | kA | |
Rated capacitance switching | 630 | A | |
Rated single capacitor bank breaking current | 1,200 | A | |
Rated interrupting time | 3 | cycles | |
Rated break time | 50 | ms | |
Rated standard operating duty | Rated operating sequence | O-CO-15s-CO O-0.3s-CO-180s-CO | |
*Standard values: further data is available on request. **Please contact Grid Solutions for special purpose, high TRV, high X/R or other ratings requirements. |