Gas-Insulated Substations up to 170 kV
GE's F35 GIS is a field-proven solution with high availability that meets the challenges of networks up to 170 kV for power generation, transmission, distribution, tertiary and heavy industry applications. The F35 is available in 72.5 kV, 145 kV and 170 kV ratings. GE’s F35 is also available SF6-free with g3-gas technology, see F35g
The F35 is a compact and accessible GIS solution, with a bay footprint below the market average. Up to 3 bays are assembled together, wired, tested and shipped enabling shorter site works. A whole F35-72,5 kV gas-insulated substation fits into the most advanced and powerful wind turbine towers, enabling them to handle more power while reducing energy losses.
In addition, the F35 is environmentally friendly and features an advanced SF6 sealing system. Full digital monitoring control and protection capabilities, and an optimized user interface enable the F35 to be readily integrated into the smart grid.
F35
Gas-Insulated Substations up to 170 kV
GE's F35 GIS is a field-proven solution with high availability that meets the challenges of networks up to 170 kV for power generation, transmission, distribution, tertiary and heavy industry applications. The F35 is available in 72.5 kV, 145 kV and 170 kV ratings. GE’s F35 is also available SF6-free with g3-gas technology, see F35g
The F35 is a compact and accessible GIS solution, with a bay footprint below the market average. Up to 3 bays are assembled together, wired, tested and shipped enabling shorter site works. A whole F35-72,5 kV gas-insulated substation fits into the most advanced and powerful wind turbine towers, enabling them to handle more power while reducing energy losses.
In addition, the F35 is environmentally friendly and features an advanced SF6 sealing system. Full digital monitoring control and protection capabilities, and an optimized user interface enable the F35 to be readily integrated into the smart grid.
Main Characteristics
Environment friendliness
- Low gas weight
- Advanced SF6 sealing system
- Smart grid features including full-digital monitoring, control and protection
- Available in g3 up to 145 kV
High availability
- One of the best experiences and high data reliability
- Current transformers outside SF6
- Drives and accessories at easy reach
- Pure-spring circuit breaker drives
Low costs of land and civil works
- One of the most compact GIS with bay footprint up to 45% below market average depending on kV rating
- Up to 2 bays (145 kV), up to 3 bays (72.5 kV), and complete bays (170 kV) assembled, wired, tested and shipped
- Isolating device for voltage transformer / surge arrester
Applicable for wind turbines at 72.5 kV
- Handle more power while reducing energy losses
- A compact HV substation fits in the wind turbine
- Withstands harsh environments
- Short installation time
Specifications
General ratings | |||
Reference electrotechnical standards | IEC/IEEE/GB | IEC/IEEE/GB | IEC/IEEE |
Voltages | 72.5 kV | 145 kV | 170 kV |
Withstand voltages | |||
- Short-duration power-frequency, phase-to-earth / across isolating distance | 140/160 kV | 275/315 kV | 325/375 kV |
- Lightning impulse, phase-to-earth / across isolating distance | 325/375 kVp | 650/750 kVp | 750/860 kVp |
Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Continuous current | up to 2500A | up to 3150A | up to 4000A |
Short-time withstand current | 31.5 kA | 40 kA | 50 kA |
Peak withstand current | 85 kAp | 100/108 kAp | 125/130 kAp |
Duration of short-circuit | 3s | 3s | 3s |
Installation | Indoor | Indoor/outdoor | Indoor |
Ambient temperature range | down to -30 / up to +55 °C | down to -30 / up to +55 °C | down to -25 / up to +55 °C |
Circuit-breaker ratings | |||
First-pole-to-clear factor | 1.5 | 1.5 | 1.5 |
Short-circuit breaking current | 31.5 kA | 40 kA | 50 kA |
Short-circuit making current | 80/82 kAp | 100/108 kAp | 125/130 kAp |
Operating sequence | O-0.3s-CO-3 min-CO/CO-15s-CO | O-0.3s-CO-3 min-CO/CO-15s-CO | O-0.3s-CO-3 min-CO/CO-15s-CO |
Drive type (three-phase or single-phase) | Pure-spring | Pure-spring | Pure-spring |
Breaking time | 50 ms | 50 ms | 50 ms |
Closing time | 70 ms | 95 ms | 100 ms |
Mechanical endurance | M2 class | M2 class | M2 class |
Capacitive switching | C2 class | C2 class | C2 class |
Disconnector and low-speed earthing switch ratings | |||
Capacitive current switching | 0.1 A | 0.1 A | 0.1 A |
Bus-transfer current switching capability | 1600/10 A / V | 2520/20 A / V | 1600/10 A / V |
Mechanical endurance | M2 class | M2 class | M2 class |
Make-proof earthing switch ratings | |||
Making current capability | 80/82 kAp | 100/108 kAp | 125/130 kAp |
Switching capability - electromagnetic coupling | 80/2 A / kV | 80/2 A / kV | 80/2 A / kV |
Switching capability - electrostatic coupling | 2/6 A / kV | 2/6 A / kV | 3/9 A / kV |
Mechanical endurance | M1 class | M1 class | M1 class |