Ready for future SF₆ gas regulations
 

Anticipating future SF₆ regulations, from 2022 onwards, GE’s versatile 420-kV SF₆-GIL are fully g³-gas compatible. This dual gas equipment allows TSOs to easily switch from SF₆ to GE’s SF₆-free g³ solution in the future.

Main Characteristics
 
Environment friendliness
  • SF₆ mass reduced by more than 15% compared to previous version
  • To go further, SF₆-free option with g³ gas allows 99 % CO2e reduction
  • At 420 kV, new SF₆-GIL launched in 2022 are g³-gas compatible
  • First-in-class gas sealing system
  • Improved tightness thanks to sealing length divided by 2 compared to previous version
Reliable experience
  • Design grounded with 50 years of experience
  • Superior know-how based on more than 200 km of GIL installed worldwide
Smart grid features
  • Full-digital monitoring (BWatch and PDWatch monitoring devices)

SF₆ Gas-Insulated Lines

At 420 kV, SF₆ today – Ready for g³ gas tomorrow
Ready for future SF₆ gas regulations
 

Anticipating future SF₆ regulations, from 2022 onwards, GE’s versatile 420-kV SF₆-GIL are fully g³-gas compatible. This dual gas equipment allows TSOs to easily switch from SF₆ to GE’s SF₆-free g³ solution in the future.

Main Characteristics
 
Environment friendliness
  • SF₆ mass reduced by more than 15% compared to previous version
  • To go further, SF₆-free option with g³ gas allows 99 % CO2e reduction
  • At 420 kV, new SF₆-GIL launched in 2022 are g³-gas compatible
  • First-in-class gas sealing system
  • Improved tightness thanks to sealing length divided by 2 compared to previous version
Reliable experience
  • Design grounded with 50 years of experience
  • Superior know-how based on more than 200 km of GIL installed worldwide
Smart grid features
  • Full-digital monitoring (BWatch and PDWatch monitoring devices)

SF₆-GIL Specifications

RATINGS     
VoltagekV253420550800
Standards 245IEC/IEEEIEC/IEEEIEC/IEEE
FrequencyHz24550/6050/6050/60
Withstand voltages, to earth
- Short-duration power-frequency
- Switching impulse
- Lightning impulse

kV
kV (peak)
kV (peak)

460
-
1050

650
1050
1425

740
1175
1550/1675

960
1550
2100
Continuous currentA4,0005,0005,000/6,0005,000
Short-time withstand currentkA63636363
Peak withstand currentkAp170170170170
Temperature°C-25/-30-30-25/-30-25/-30
 

g³ gas GIL Specifications 

RATINGS   
VoltagekV362420
Standards IEC/IEEEIEC/IEEE
FrequencyHz50/6050/60
Withstand voltages, to earth
- Short-duration power-frequency
- Switching impulse
- Lightning impulse

kV
kV (peak)
kV (peak)

520
950
1175

650
1050
1425
Continuous currentA4,000/5,0004,000/5,000
Short-time withstand currentkA6363
Peak withstand currentkAp170170
Temperature°C-30-25

Applications 

Sellindge SubstationSSEN_SF₆-free-New-Deer_Substation
420 kV SF₆ GIL - Total length: 17,000 m420 kV SF₆ GIL - Total length: 15,000 m

 

SSEN_SF₆-free-New-Deer_SubstationSellindge Substation
550 kV SF₆ GIL - Total length: 5,900 m420 kV SF₆ GIL - Total length: 2,500 m
Sellindge SubstationSellindge Substation
245 kV SF₆ GIL - Total length: 2,100 m362 kV SF₆ GIL in shaft (140 m high) - Total length: 900m