Better for the grid, better for the planet
  • SF₆-free with g³, GE's game changing alternative to SF₆ as insulating medium enables a reduction of 99% of global warming potential
  • First-in-class gas sealing system
  • g³-420 kV GIL is a dual gas busbar system also compatible with SF₆. It allows TSO to still use SF₆ while being ready for up-coming regulations.
  • Improved tightness thanks to sealing length divided by 2 compared to previous version
Field-proven experience
  • Design grounded with 50 years of experience acquired with SF₆ gas insulated lines
  • g³ gas–insulated lines were the World first 420 kV SF₆-free GIL on the market (2015) and the first g³ product available on the market
  • Since then, some 10 sites – 5000+ meters
Smart grid features
  • Full-digital monitoring (BWatch and PDWatch monitoring devices)

SF₆-free Gas-Insulated Lines

SF₆-free g³ Gas-Insulated Lines
For electrical networks up to 420 kV
Better for the grid, better for the planet
  • SF₆-free with g³, GE's game changing alternative to SF₆ as insulating medium enables a reduction of 99% of global warming potential
  • First-in-class gas sealing system
  • g³-420 kV GIL is a dual gas busbar system also compatible with SF₆. It allows TSO to still use SF₆ while being ready for up-coming regulations.
  • Improved tightness thanks to sealing length divided by 2 compared to previous version
Field-proven experience
  • Design grounded with 50 years of experience acquired with SF₆ gas insulated lines
  • g³ gas–insulated lines were the World first 420 kV SF₆-free GIL on the market (2015) and the first g³ product available on the market
  • Since then, some 10 sites – 5000+ meters
Smart grid features
  • Full-digital monitoring (BWatch and PDWatch monitoring devices)

Positive impact of 100 meters SF₆-free GIL

Calculate the CO2e reduction of my project with GE's g³ CO2 equivalent calculator

g³ gas GIL Specifications

RATINGS   
VoltagekV362420
Standards IEC/IEEEIEC/IEEE
FrequencyHz50/6050/60
Withstand voltages, to earth
- Short-duration power-frequency
- Switching impulse
- Lightning impulse

kV
kV (peak)
kV (peak)

650
1050
1425

650
1050
1425
Continuous currentA4,000/5,0004,000/5,000
Short-time withstand currentkA6363
Peak withstand currentkAp170170
Temperature°C-30-25/-30

Applications

NATIONAL GRID, UK - Sellindge Substation, 230 m of 420 kV GIL, 63 kA, 4000 A, The world first SF₆-free g³ GIL
SP ENERGY NETWORKS, UK - Kilmarnock Substation, 177 m of 420 kV SF₆-free g³ GIL, 63 kA, 4000 A
SSEN TRANSMISSION, UK - New Deer Substation, 1020 m of 420 kV GIL, 40 kA, 4000 A, The longest SF₆-free g³ GIL in operation