Delivering speed and security for advanced transmission line protection.
Delivering speed and security for advanced transmission line protection.
Manufacturing for C90Plus Bay Controller has been discontinued. As an alternative, please refer to the C60 with Firmware 7.7 or newer and User Interface Option E: 7” Graphical Front Panel Display.
Manufacturing for C90Plus Bay Controller has been discontinued. As an alternative, please refer to the C60 with Firmware 7.7 or newer and User Interface Option E: 7” Graphical Front Panel Display.
The C90Plus bay control or monitoring functionality is intended for high-end bay control applications typically used in transmission installations, where a larger quantity of I/O, advanced protection and control functionality and an advanced HMI is desired.
Easy to use system where settings and priorities can be configured within seconds
Conventional frequency and voltage load shedding schemes operate typically between 250ms to seconds. Contingency-based load shedding schemes are typically faster at 160 – 400 ms, depending on both system architecture and communications employed. Both these scheme types are too slow for industrial cogeneration applications such as oil and gas or manufacturing, where very fast load shedding is required for power system and critical process integrity.
Digital fault recorder summary with the latest information on the events, faults, transients and disturbances.
There are three recorders available within the C90Plus that eliminate the need for other stand-alone recording equipment. The transient recorder allows for a high sampling rate usually to capture power system faults and system transients. The disturbance recorder is used to capture longer records in order to understand issues such as voltage sags or swells. Lastly, the C90Plus is equipped with a powerful and accurate Sequence of Event (SOE) recorder. Information for all three recorders can be accessed either through the front panel HMI or through EnerVista™ Launchpad Software.
The C90Plus supports an advanced automation logic engine that supports Boolean operators, analog comparisons, and advanced mathematical operations.
The C90Plus provides for secure remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The availability of three independently configurable Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner. The C90Plus supports the most popular industry standard protocols enabling easy, direct integration into SCADA systems.
HMI Display
Security
The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the C90Plus relay. The EnerVista™suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the C90Plus into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. Learn More
Access Control
Multilin devices and relays are designed with simple but powerful security to enable reliability and compliance for virtually any project or implementation. With support for multi-level permissions and multi-factor supervisory controls, Multilin devices can help you manage the integrity of your system during commissioning, testing, implementation, and beyond. The UR and URPlus families provide separate authentication for settings and commands to the system. In addition, as discrete authentications for local and remote access they also provide supervisory control factor that can lock or unlock a device for configuration changes and other modifications.
Intrusion Detection
Multilin’s family of protection and control products can also help enable your security perimeter and intrusion detection programs. By providing essential alarming and logging of critical events, Multilin devices can help you detect potential breaches within your system and allow you to respond quickly and effectively. Specifically, unsuccessful access attempts are logged, alarmed, and lead to potential attackers being locked out. This ensures the reliability of your system during questionable activity, and a control factor that can lock or unlock a device for configuration changes and other modifications.
Auditing and Reporting
With the security audit trail reporting feature and support for event logging of key activities such as configuration changes, Multilin devices can help ensure device and protection system integrity, and perform forensic auditing of activities and changes for compliance.
The C90Plus Automation Control System with fast load shed is a powerful automation control system that eliminates the need for several separate devices. Performing intelligent high-end and fast optimal load shedding, the C90Plus is highly customizable and scalable.
New small signal oscillation detection protection element. With increasingly large interconnected power systems, one of the technical challenges is the inter-area low frequency oscillations. Inter-area oscillations not only limit the amount of power transfer, but also threaten system security and equilibrium, as they may lead to system instability and cascading outages. Therefore, it is essential to identify the characteristics of the inter-area oscillations, including oscillation frequency and damping ratio, so that proper actions can be taken based on the results. This is required to improve system damping and maintain stability in the power system. The C90Plus can detect these inter-area oscillations and provide an alarm or even trip signal to prevent a large-scale system disturbance.
Support for alphanumeric passwords as per the CIP-007-02 cyber security standard.